CODE: INDIAN ELECTRICITY RULES/ CENTRAL ELECTRICITY AUTHORITY:
RIGHT OF WAY CLEARANCE (AS PER GETCO STANDARD):
KV
Min ROW
66 KV
18 Meter
132 KV
27 Meter
220 KV
35 Meter
400KV
52 Meter (Single Circuit)
400 KV
48 Meter (Double Circuit)
MINIMUM CLEARANCES BETWEEN ELECTRICAL LINES CROSSING EACH OTHER:
Voltage
66 KV
132 KV
220 KV
400 KV
66 KV
2.4 Meter
3 Meter
4.5 Meter
5.4 Meter
132 KV
3 Meter
3 Meter
4.5 Meter
5.4 Meter
220 KV
4.5 Meter
4.5 Meter
4.5 Meter
5.4 Meter
400 KV
4.5 Meter
5.4 Meter
5.4 Meter
5.4 Meter
PERMISSIBLE MIN GROUND CLEARANCE OF ELECTRICAL LINE:
KV
Ground Clearance
Over National Highway
66 KV
6.1 Meter
8.0 Meter
132 KV
6.1 Meter
8.6 Meter
220 KV
7.0 Meter
9.8 Meter
400KV
8.8 Meter
10.8 Meter
CLEARANCE FOR TELEPHONE LINE CROSSINGS POWER LINE:
KV
Clearance (Min)
66 KV
2.4 Meter
132 KV
2.7 Meter
220 KV
3.0 Meter
VERTICAL CLEARANCE BETWEEN ELECTRICAL LINE AND RAILWAY TRACKS.
KV
Clearance (Min)
66 KV
14 Meter
132 KV
14.6 Meter
220 KV
15.4 Meter
400 KV
17.9 Meter
CLEARANCE FROM BUILDINGS TO LOW, MEDIUM & HIGH VOLTAGE LINES:
Voltage Description Distance Low & Medium Voltage Flat roof, open balcony, verandah roof ,When the line passes above the building a vertical clearance from the highest point 2.5 Meter Low & Medium Voltage Line passes adjacent to the building a horizontal clearance from the nearest point 1.2 Meter Low & Medium Voltage Line passes above the building a vertical clearance 2.5 Meter Low & Medium Voltage Line passes adjacent the building a Horizontal clearance 1.2 Meter 11 KV to 33 KV Line passes above or adjacent to any building or part of a building 3.7 Meter Above 33 KV Line passes above or adjacent to any building or part of a building 3.7+(0.3 for every additional 33 KV ) Up to 11 KV The horizontal clearance between the nearer conductor and any part of such building 1.2 Meter 11 KV to 33 KV The horizontal clearance between the nearer conductor and any part of such building 2.0 Meter Above 33 KV The horizontal clearance between the nearer conductor and any part ofsuch building 2.0 + (0.3 for every additional 33 KV )
CLEARANCE ABOVE GROUND AT THE LOWEST CONDUCTOR:
Voltage Description Distance Low & Medium Voltage Across a street 5.8 Meter High Voltage Across a street 6.1 Meter Low & Medium Voltage Along a street 5.5 Meter High Voltage Along a street 5.8 Meter Low & Medium Voltage Elsewhere than along or across any street 4.0 Meter High Voltage Elsewhere than along or across any street 5.2 Meter 33 KV & EHV Clearance above ground(Add 0.3 Meter for every 33 KV Volts in 5.2 Meter) Min 6.1 Meter
VERTICAL CLEARANCE AT MIDDLE OF SPAN:
Span
Vertical Clearance (At Middle of Span)
200 Meter
4.0 Meter
300 Meter
5.5 Meter
400 Meter
7.0 Meter
500 Meter
8.5 Meter
SAFETY CLEARANCE FROM LIVE PART IN OUTDOOR SUBSTATION:
KV
Safety Working Clearance
12 KV
2.6 Meter
36 KV
2.8 Meter
72.5 KV
3.1 Meter
145 KV
3.7 Meter
220 KV
4.3 Meter
400KV
6.4 Meter
800 KV
10.3 Meter
LYING OF TELECOMMUNICATION CABLES WITH POWER CABLES (>33 KV).
Cable
Min. Distance
Power cable of voltage exceeding 33 kV shall be laid
Min 1.2 Meter depth
Underground telecommunication cable shall be with underground power cable of voltage exceeding 33 kV.
Min 0.6 Meter Separate from Power Cable
SAFE APPROACH LIMITS FOR PEOPLE:
Voltage
214V to 415 KV
11KV
33KV
66KV
132KV
275KV
Person using manually operated tool 1.3 Meter 2.0 Meter 3.0 Meter 4.0 Meter 5.0 Meter 6.0 Meter Person using power operated tool 3.0 Meter 3.0 Meter 3.0 Meter 4.0 Meter 5.0 Meter 6.0 Meter