Electrical Safety Clearance (Qatar General Electricity) (Part-1)
ELECTRICAL SAFETY CLEARANCE (QATAR GENERAL ELECTRICITY) (PART-1)
STANDARD: QATAR GENERAL ELECTRICITY & WATER CORPORATION
MINIMUM SAFETY CLEARANCE OF PIPELINES FROM ELECTRICAL TOWER:
Description
Voltage
33KV/66KV/132KV
220KV/400KV
The right of way (ROW) (widths on either side of the center line of overhead transmission lines )
25 Meter
50 Meter
Other than the roadways and boundary fences of security establishments any temporary or permanent structures / buildings, parapet walls,
Not within 25 Meter
Not within 50 Meter
With All Underground services crossing the way leave (from the nearest tower foundation)
35 Meter (Min)
50 Meter (Min)
The nearest side of the road reservation to the nearest tower foundation
25 Meter
35 Meter,50 Meter
The pipelines (water, oil/gas etc.) crossing (respectively away from the nearest base of tower leg). Pipe-lines shall not be laid parallel to the overhead line within the limits of a way leave (ROW).
25 Meter (Min)
35 Meter(Min) ,50 Meter(Min)
Cables crossing the transmission lines way leave (ROW) respectively away from the nearest base of tower leg.
25 Meter
35 Meter,50 Meter
Foundations and civil structures (Temporary or permanent) will not be permitted in the close proximity to the cable circuit. A minimum horizontal distance from such structures to the nearest edge of the cable trench shall be observed
Min 1.5 Meter
Min 1.5 Meter
CLEARANCE AMONG ELECTRICAL LINE-TELEPHONE- WATER-SEWERAGE -GAS LINE
Service
Vertical Clearance(Min) Water Line (to cross below EHV cable level) 0.5 Meter Sewerage Mains (to cross below EHV cable level) 1.0 Meter Drainage Mains (to cross below EHV cable level) 0.5 Meter Gas pipes 0.6 Meter Telephone lines 0.5 Meter LV / 11kV cables 0.5 Meter
SAFETY CLEARANCE FOR EXCAVATION OF LAND :
Type of Excavation
Distance Use of heavy mechanical excavators (other than hand operated pneumatic jack hammers) or driving sheet piles Not less than 3 Meter from the edge of cable, cover, cable joint Heavy machinery engaged in the civil construction or road works operating load/thrust/ weight will not be applied directly on the cable installation Trench excavations parallel to the cable installations Minimum separation of 1 Meter to the nearest edge of cable tile Laying of metal pipes over a long distance parallel to cable Not permitted unless the Step and Touch Potentials at any point of the pipe line do not exceed 65 Volts.
(A) INSIDE TOWNS
DISTANCE BETWEEN TOWER’S FOUNDATION TO PIPELINE IN PARALLEL AND INTERSECTIONS.
Voltage
Min Distance
380/220V
0.5 Meter
20KV
2 Meter
63KV
7 Meter
132KV
10 Meter
230KV and Above
20 Meter
DISTANCE BETWEEN UNDERGROUND POWER CABLES TO WALL OF GAS PIPELINES IN PARALLEL ROUTES.
Voltage
Min Horizontal Distance
Min Vertical Distance
380/220V
1 Meter
0.5 Meter
20KV
2 Meter
1 Meter
63KV
3 Meter
1.5 Meter
(B) OUTSIDE OF TOWNS:
DISTANCE BETWEEN TOWER’S FOUNDATION TO PIPELINE IN PARALLEL AND INTERSECTIONS.
KV
Min Distance in Parallel Route (Up to 5 Km)
Min Distance in Parallel Route (Above 5 Km)
20KV
20 Meter
30 Meter
63KV
30 Meter
40 Meter
132KV
40 Meter
50 Meter
230KV
50 Meter
60 Meter
400KV
60 Meter
60 Meter
DISTANCE BETWEEN OVERHEAD LINES TO GAS PIPELINES AT INTERSECTIONS.
KV
Min Distance
20KV
8 Meter
63KV
9 Meter
132KV
10 Meter
230KV
11 Meter
400KV
12 Meter
DISTANCE BETWEEN TOWER’S FOUNDATIONS TO GAS PIPELINES AT INTERSECTIONS.
KV
Min Distance
20KV
20 Meter
63KV and Higher
30 Meter
RIGHT OF WAY (R.O.W) FROM ROADS:
Highway
Distance
High Way : (38 meter from one side of Central Line of Highway)
76 Meter
First Class State Road=(22.5 meter from one side of Central Line of Highway)
45 Meter
Second Class State Road=(17.5 meter from one side of Central Line of Highway)
35 Meter
Third Class State Road =(12.5 meter from one side of Central Line of Highway)
25 Meter
Forth Class State Road=(7.5 meter from one side of Central Line of Highway)
15 Meter
GENERAL ELECTRICAL SAFETY CLEARANCE:
KV
Description
Distance
Up to 11 KV
At points where the lines cross roads or railways
Min 6 Meter Height
Up to 11 KV
parallel to roads the
Min 5.5 Meter Height
Up to 11 KV
lines cross totally desert regions where no traffic is possible
Min 5.5 Meter Height
20 KV to 66 KV
All Location
Min 6 Meter Height
Up to 11 KV
Conductor Joint
No joint shall be closer than 3 meters to a point of support
33 KV & 66 KV
Conductor Joint
No tension joints shall be used unless specially approved.