Indian Electricity Rules-Abstract.
INDIAN ELECTRICITY RULES-ABSTRACT
February 22, 2014 1 Comment
ABSTRACT OF INDIAN ELECTRICITY RULES:
- CUT-OUT ON CONSUMER’S PREMISES:
- The supplier shall provide a suitable cut-out in each conductor of every service-line other than an earthed or earthed neutral conductor or the earthed external conductor of a concentric cable within a consumer’s premises, in an accessible position. Such cut-out shall be contained within an adequately enclosed fireproof receptacle. * Where more than one consumer is supplied through a common service-line, each such consumer shall be provided with an independent cut-out at the point of junction to the common service * Every electric supply line other than the earth or earthed neutral conductor of any system or the earthed external conductor of a concentric cable shall be protected by a suitable cut-out by its owner * No cut-out, link or switch other than a linked switch arranged to operate simultaneously on the earthed or earthed neutral conductor and live conductors shall be inserted or remain inserted in any earthed or earthed neutral conductor of a two wire-system or in any earthed or earthed neutral conductor of a multi-wire system or in any conductor connected thereto with the following exceptions:(a) A link for testing purposes, or (b) A switch for use in controlling a generator or transformer.
- DANGER NOTICES:
- The owner of every medium, high and extra-high voltage installation shall affix permanently in a conspicuous position a danger notice in Hindi or English and the local language of the district, with a sign of skull and Bones on * (a) Every motor, generator, transformer and other electrical plant and equipment together with apparatus used for controlling or regulating the same; * (b) All supports of high and extra-high voltage overhead lines which can be easily climb-upon without the aid of ladder or special appliances.
- CABLES :
- Flexible cables shall not be used for portable or transportable motors, generators, transformer rectifiers, electric drills, electric sprayers, welding sets or any other portable or transportable apparatus unless they are heavily insulated and adequately protected from mechanical injury. * Where the protection is by means of metallic covering, the covering shall be in metallic connection with the frame of any such apparatus and earth. * The cables shall be three core type and four-core type for portable and transportable apparatus working on single phase and three phases supply respectively and the wire meant to be used for ground connection shall be easily Identifiable * Where A.C. and D.C. circuits are installed on the same support they shall be so arranged and protected that they shall not come into contact with each other when live.
- SAFETY:
- Two or more gas masks shall be provided conspicuously and installed and maintained at accessible places in every generating station with capacity of 5 MW and above and enclosed sub-station with transformation capacity of 5 MVA and above for use in the event of fire or smoke. * Provide that where more than one generator with capacity of 5 MW and above is installed in a power station, each generator would be provided with at least two separate gas masks in accessible and conspicuous position.
- HIGH VOLTAGE EQUIPMENT INSTALLATIONS
- High Voltage equipment shall have the IR value as stipulated in the relevant Indian Standard. * At a pressure of 1000 V applied between each live conductor and earth for a period of one minute the insulation resistance of HV installations shall be at least 1 Mega ohm Medium and Low Voltage Installations- At a pressure of 500 V applied between each live conductor and earth for a period of one minute, the insulation resistance of medium and low voltage installations shall be at least 1 Mega ohm
- SWITCHBOARD SHALL COMPLY WITH THE FOLLOWING PROVISIONS :
- A clear space of not less than 1 meter in width shall be provided in front of the switchboard; * If there are any attachments or bare connections at the back of the switchboard, the space (if any) behind the switchboard shall be either less than 20 centimeters or more than 75 centimeters in width, measured from the farthest outstanding part of any attachment or conductor; * If the space behind the switchboard exceeds 75 centimeters in width, there shall be a passage-way from either end of the switchboard clear to a height of 1.8 meters.
- DECLARED VOLTAGE OF SUPPLY TO CONSUMER:
- In the case of low or medium voltage, by more than 6 per cent, or; * In the case of high voltage, by more than 6 per cent on the higher side or by more than 9 per cent on the lower side, or; * In the case of extra-high voltage, by more than 10 per cent on the higher side or by more than 12.5 per cent on the lower side.
- DECLARED FREQUENCY OF SUPPLY TO CONSUMER
- Except with the written consent of the cons…