2. Calculate IDMT over Current Relay Setting (50/51)
CALCULATE IDMT OVER CURRENT RELAY SETTING (50/51)
- Calculate setting of IDMT over Current Relay for following Feeder and CT Detail * Feeder Detail: Feeder Load Current 384 Amp, Feeder Fault current Min11KA and Max 22KA. * CT Detail: CT installed on feeder is 600/1 Amp. Relay Error 7.5%, CT Error 10.0%, CT over shoot 0.05 Sec, CT interrupting Time is 0.17 Sec and Safety is 0.33 Sec. * IDMT Relay Detail: * IDMT Relay Low Current setting: Over Load Current setting is 125%, Plug setting of Relay is 0.8 Amp and Time Delay (TMS) is 0.125 Sec, Relay Curve is selected as Normal Inverse Type. * IDMT Relay High Current setting :Plug setting of Relay is 2.5 Amp and Time Delay (TMS) is 0.100 Sec, Relay Curve is selected as Normal Inverse Type
CALCULATION OF OVER CURRENT RELAY SETTING:
(1) LOW OVER CURRENT SETTING: (I>)
- Over Load Current (In) = Feeder Load Current X Relay setting = 384 X 125% =480 Amp * Required Over Load Relay Plug Setting= Over Load Current (In) / CT Primary Current * Required Over Load Relay Plug Setting = 480 / 600 = 0.8 * Pick up Setting of Over Current Relay (PMS) (I>)= CT Secondary Current X Relay Plug Setting * Pick up Setting of Over Current Relay (PMS) (I>)= 1 X 0.8 = 0.8 Amp * Plug Setting Multiplier (PSM) = Min. Feeder Fault Current / (PMS X (CT Pri. Current / CT Sec. Current)) * Plug Setting Multiplier (PSM) = 11000 / (0.8 X (600 / 1)) = 22.92 * Operation Time of Relay as per it’s Curve * Operating Time of Relay for Very Inverse Curve (t) =13.5 / ((PSM)-1). * Operating Time of Relay for Extreme Inverse Curve (t) =80/ ((PSM)2 -1). * Operating Time of Relay for Long Time Inverse Curve (t) =120 / ((PSM) -1). * Operating Time of Relay for Normal Inverse Curve (t) =0.14 / ((PSM) 0.02 -1). * Operating Time of Relay for Normal Inverse Curve (t)=0.14 / ( (22.92)0.02-1) = 2.17 Amp * Here Time Delay of Relay (TMS) is 0.125 Sec so * Actual operating Time of Relay (t>) = Operating Time of Relay X TMS =2.17 X 0.125 =0.271 Sec * Grading Time of Relay = [((2XRelay Error)+CT Error)XTMS]+ Over shoot+ CB Interrupting Time+ Safety * Total Grading Time of Relay=[((2X7.5)+10)X0.125]+0.05+0.17+0.33 = 0.58 Sec * Operating Time of Previous upstream Relay = Actual operating Time of Relay+ Total Grading Time Operating Time of Previous up Stream Relay = 0.271 + 0.58 = 0.85 Sec
(2) HIGH OVER CURRENT SETTING: (I>>)
- Pick up Setting of Over Current Relay (PMS) (I>>)= CT Secondary Current X Relay Plug Setting * Pick up Setting of Over Current Relay (PMS) (I>)= 1 X 2.5 = 2.5 Amp * Plug Setting Multiplier (PSM) = Min. Feeder Fault Current / (PMS X (CT Pri. Current / CT Sec. Current)) * Plug Setting Multiplier (PSM) = 11000 / (2.5 X (600 / 1)) = 7.33 * Operation Time of Relay as per it’s Curve * Operating Time of Relay for Very Inverse Curve (t) =13.5 / ((PSM)-1). * Operating Time of Relay for Extreme Inverse Curve (t) =80/ ((PSM)2 -1). * Operating Time of Relay for Long Time Inverse Curve (t) =120 / ((PSM) -1). * Operating Time of Relay for Normal Inverse Curve (t) =0.14 / ((PSM) 0.02 -1). * Operating Time of Relay for Normal Inverse Curve (t)=0.14 / ( (7.33)0.02-1) = 3.44 Amp * Here Time Delay of Relay (TMS) is 0.100 Sec so * Actual operating Time of Relay (t>) = Operating Time of Relay X TMS =3.44 X 0.100 =0.34 Sec * Grading Time of Relay = [((2XRelay Error)+CT Error)XTMS]+ Over shoot+ CB Interrupting Time+ Safety * Total Grading Time of Relay=[((2X7.5)+10)X0.100]+0.05+0.17+0.33 = 0.58 Sec * Operating Time of Previous upstream Relay = Actual operating Time of Relay+ Total Grading Time. * Operating Time of Previous up Stream Relay = 0.34 + 0.58 = 0.85 Sec
CONCLUSION OF CALCULATION:
- Pickup Setting of over current Relay (PMS) (I>) should be satisfied following Two Condition. * (1) Pickup Setting of over current Relay (PMS)(I>) >= Over Load Current (In) / CT Primary Current * (2) TMS <= Minimum Fault Current / CT Primary Current * For Condition (1) 0.8 > =(480/600) = 0.8 >= 0.8, Which found OK * For Condition (2) 0.125 <= 11000/600 = 0.125 <= 18.33, Which found OK * Here Condition (1) and (2) are satisfied so * Pickup Setting of Over Current Relay = OK * Low Over Current Relay Setting: (I>) = 0.8A X In Amp * Actual operating Time of Relay (t>) = 0.271 Sec * High Over Current Relay Setting: (I>>) = 2.5A X In Amp * Actual operating Time of Relay (t>>) = 0.34 Sec